I have the following set up with the DNO at 17Kwh import & 8Kwh export.
Battery Fox ESS 62.16 kWh Total Battery Storage 6 x EP11
FoxESS K Series Hybrid Inverter 18kW of Inverter Power Fox ESS 2 x KH9 throttled back to 8.5kwh import & export 4kwh per inverter.
2 x Fox HV Junction Box
There are 3 x EP11 to HV Juntion Box coneted to FoxESS K Series KH9
On a 3 hour export time what will the out put be I,m only getting 16Kwh from 1600 to 1900hrs there is an average of 2.50kwh off solar and 560watt used on home. I think it sould be around 24kwh / I do get the full 17kwh on import.
Fox updated my firm ware 2 days ago / The export Kwh are stopping starting power 60wats to 7Kwh
Please help
Dave Jenkins
Can you post a video or photos of what the inverter screen is doing during the export and a screenshot of your export setting configured in the mode scheduler.
Community Admin / FoxESS Elite Professional
Buy me a coffee or Book a zoom meeting for remote consultancy
FoxESS Tri Inverter Installation
2 x KH & 1 x H1
24 x HV2600 (62.4kWh)
32 x 490w across 4 arrays
Dual Tesla Household
Heatpump & Low Carbon Housebuild
Buy me a coffee or Book a zoom meeting for remote consultancy
FoxESS Tri Inverter Installation
2 x KH & 1 x H1
24 x HV2600 (62.4kWh)
32 x 490w across 4 arrays
Dual Tesla Household
Heatpump & Low Carbon Housebuild
Hi Will
Here are the settings on my fox app for export.
I save then submit then return on each one.
I will film the inverters tommorow when there exporting
I noticed today the slave batteries are charging from the Master/Slave inverter when the exporting stops?
Here are the settings on my fox app for export.
I save then submit then return on each one.
I will film the inverters tommorow when there exporting
I noticed today the slave batteries are charging from the Master/Slave inverter when the exporting stops?
Attachments:
So you're instructing your inverter to output 4.1kW, remember that this includes house loads so if you house used 2kW you would only be exporting 2kW in this 4kW example.
Can you share any details of where you think the problem is and why you believe there to be a problem?
Can you share any details of where you think the problem is and why you believe there to be a problem?
Community Admin / FoxESS Elite Professional
Buy me a coffee or Book a zoom meeting for remote consultancy
FoxESS Tri Inverter Installation
2 x KH & 1 x H1
24 x HV2600 (62.4kWh)
32 x 490w across 4 arrays
Dual Tesla Household
Heatpump & Low Carbon Housebuild
Buy me a coffee or Book a zoom meeting for remote consultancy
FoxESS Tri Inverter Installation
2 x KH & 1 x H1
24 x HV2600 (62.4kWh)
32 x 490w across 4 arrays
Dual Tesla Household
Heatpump & Low Carbon Housebuild
Hi Wil
The inverters are only set at 4.1kwI had them on 4kw for export
8.5kw for import
There both Fox H1 9.0kW Hybrid Inverter G2. I though that would be the full 9kw to use normaly.
The inverters are only set at 4.1kwI had them on 4kw for export
8.5kw for import
There both Fox H1 9.0kW Hybrid Inverter G2. I though that would be the full 9kw to use normaly.
Can I put the Import & Export output to 9kw & let the inverter throttling set to the DNO limits?