Thanks so much, it is now all updated.
lets hope for some sun later this week.
FYI of the 52 panels we have, only 7 on one mppt and 6 on another are currently connected. the other 39 are due to be connected early January. today for a short time we pulled in circa 3kw.
before we had 2 x H1-6kw ...
Search found 19 matches
- Mon Dec 30, 2024 6:16 pm
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
- Mon Dec 30, 2024 10:38 am
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
Re: H3 Pro issue- Power from Load icon
Good Morning. all seems to be well this morning, thank you so much.
See the image below of the firmware.
Master 1.31 Slave 1.06, Manager 1.15
I did think maybe the the firmware might need updating but i looking online and could not see how to update it.
See the image below of the firmware.
Master 1.31 Slave 1.06, Manager 1.15
I did think maybe the the firmware might need updating but i looking online and could not see how to update it.
- Sun Dec 29, 2024 4:00 pm
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
Re: H3 Pro issue- Power from Load icon
Hiya. i re-tested the meter a few times today and all is well, meter read OK when tested so looking good.
Hope you don't mind re re asking.
Ref the Chint PT , it is currently set to "1" after reading the Chint instructions i wonder if "1" is correct?
I am still a little concerned about the Gid ...
Hope you don't mind re re asking.
Ref the Chint PT , it is currently set to "1" after reading the Chint instructions i wonder if "1" is correct?
I am still a little concerned about the Gid ...
- Sun Dec 29, 2024 10:45 am
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
Re: H3 Pro issue- Power from Load icon
Thanks David, a greet reply.
The sun has not been shining much recently and so the batteries are low, however they have been charged via the grid during this issue we are discussing.
I checked the "Meter test" last night and it said "Meter Correct"
This morning i checked it again and it now says ...
The sun has not been shining much recently and so the batteries are low, however they have been charged via the grid during this issue we are discussing.
I checked the "Meter test" last night and it said "Meter Correct"
This morning i checked it again and it now says ...
- Sun Dec 29, 2024 8:44 am
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
Re: H3 Pro issue- Power from Load icon
Good Morning David. Hope you are having a good weekend. My good friend came over yesterday and assisted with the clamp meter readings.
we didn't have much time but we did discover that the clamp meter reading on the tails did not match the meter or what was on the invertor.
We also discovered ...
we didn't have much time but we did discover that the clamp meter reading on the tails did not match the meter or what was on the invertor.
We also discovered ...
- Sat Dec 28, 2024 10:10 am
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
Re: H3 Pro issue- Power from Load icon
Thanks Dave.
I have swapped the CT pairs over to match the above/
Red on 1,4 & 7 and black on 3,6 & 9, N on 10.
L1 Brown on 31, Line 2 Black on 33 and Line 3 Grey on 36
Sorry to say it is still no better. I have a mate coming over later to assist with the "Clamp Meter check" so will advise later ...
I have swapped the CT pairs over to match the above/
Red on 1,4 & 7 and black on 3,6 & 9, N on 10.
L1 Brown on 31, Line 2 Black on 33 and Line 3 Grey on 36
Sorry to say it is still no better. I have a mate coming over later to assist with the "Clamp Meter check" so will advise later ...
- Fri Dec 27, 2024 1:31 pm
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
Re: H3 Pro issue- Power from Load icon
Thanks David. Off to to Bristol to see a panto shortly.
I do have a clamp meter and will check the connections tomorrow.
The CT red wires are connected to 2 6 & 9, black to 1,4 & 7. each phase to 31,33 & 36. Neut to 10. should i swap the red/black over?
I think it seems we are making good ...
I do have a clamp meter and will check the connections tomorrow.
The CT red wires are connected to 2 6 & 9, black to 1,4 & 7. each phase to 31,33 & 36. Neut to 10. should i swap the red/black over?
I think it seems we are making good ...
- Fri Dec 27, 2024 11:49 am
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
Re: H3 Pro issue- Power from Load icon
Do you think these look OK. do i need to check anything?
- Fri Dec 27, 2024 10:47 am
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
Re: H3 Pro issue- Power from Load icon
Cheers Dave, i have to say how super helpful you are. I simply would not be getting anywhere without you.
I have checked and see below
UA 244.9V
UB 246.0V
UC 249.3V
1A 26.00A
1B 26.16A
1C 22.96A
PT 0644kw
PA -3.468kw
PB 6.480kw
PC -2.404kw
00134.15KWH
00060.020KWH
00073.95KWH
n1-9600
----001 ...
I have checked and see below
UA 244.9V
UB 246.0V
UC 249.3V
1A 26.00A
1B 26.16A
1C 22.96A
PT 0644kw
PA -3.468kw
PB 6.480kw
PC -2.404kw
00134.15KWH
00060.020KWH
00073.95KWH
n1-9600
----001 ...
- Thu Dec 26, 2024 10:46 pm
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
Re: H3 Pro issue- Power from Load icon
i have taken a look at the "communication" settings in the H3 , device 1 set at address 247 and device 2 at 1. so i swapped these and still no good.. seems that device 1 previously set on 247 was able to communicate with the Chint meter OK but still report "Meter wrong"
i also changed the Chint ...
i also changed the Chint ...
- Thu Dec 26, 2024 10:20 pm
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
Re: H3 Pro issue- Power from Load icon
Thanks Dave.
I have now set Protocol to N1.
I changed the CT to 50 from 40 and i can then get the meter check to work and the meter check says meter correct, however s few seconds later the meter check fails, all during this the invertor is playing up very badly. now set back to 40
below is a ...
I have now set Protocol to N1.
I changed the CT to 50 from 40 and i can then get the meter check to work and the meter check says meter correct, however s few seconds later the meter check fails, all during this the invertor is playing up very badly. now set back to 40
below is a ...
- Thu Dec 26, 2024 7:49 pm
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
Re: H3 Pro issue- Power from Load icon
another screenshot, now pulling huge KW's
- Thu Dec 26, 2024 7:46 pm
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
Re: H3 Pro issue- Power from Load icon
Cheers Dave, i fully understand all except the part below (all the other items re set correctly as you have said
"The rest of the settings look correct it should be set to ‘modbus’ and 9600, n, 8, 1 - address 001"
9600 is OK
Address 001 is OK
Not sure about "modbus" i don't see an option for ...
"The rest of the settings look correct it should be set to ‘modbus’ and 9600, n, 8, 1 - address 001"
9600 is OK
Address 001 is OK
Not sure about "modbus" i don't see an option for ...
- Thu Dec 26, 2024 6:05 pm
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
Re: H3 Pro issue- Power from Load icon
HI Dave, another screenshot, i don't see an option to alter the meter settings, its either on or off.
- Thu Dec 26, 2024 2:41 pm
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
Re: H3 Pro issue- Power from Load icon
Thanks Again Dave.
I have set CT to 40 and 50 and still no good.
Just for clarity, could you advise (if possible) what the DTSU666 settings should be for the following.
CT Currently set to 40/50
PT Currently set to 1
Prot Currently set to N1
Add Currently set to 1
Baud Currently set to9600
Net ...
I have set CT to 40 and 50 and still no good.
Just for clarity, could you advise (if possible) what the DTSU666 settings should be for the following.
CT Currently set to 40/50
PT Currently set to 1
Prot Currently set to N1
Add Currently set to 1
Baud Currently set to9600
Net ...
- Thu Dec 26, 2024 11:40 am
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
Re: H3 Pro issue- Power from Load icon
Thanks Dave.
the Meter is a DTSU666
here are some images of the invertor running screen, (METER is currently disabled in the H3 Pro as when enables that's when the inverter plays up.
when in the inverter meter setting there is an option to "check Meter" which returns "Meter Wrong"
the Meter is a DTSU666
here are some images of the invertor running screen, (METER is currently disabled in the H3 Pro as when enables that's when the inverter plays up.
when in the inverter meter setting there is an option to "check Meter" which returns "Meter Wrong"
- Thu Dec 26, 2024 10:05 am
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
Re: H3 Pro issue- Power from Load icon
HI Dave. thanks so much for posting a response, can i check?
how do i set the invertor meter settings to be 3 phase. it only has setting for Meter 1 and Meter 2. also when looking at running/Grid. it shows all 3 phases R,S & T
Does the DTSU666 need to be setup for use with 3 phase? if so any idea ...
how do i set the invertor meter settings to be 3 phase. it only has setting for Meter 1 and Meter 2. also when looking at running/Grid. it shows all 3 phases R,S & T
Does the DTSU666 need to be setup for use with 3 phase? if so any idea ...
- Tue Dec 24, 2024 4:09 pm
- Forum: Customer/End User Help
- Topic: H3 Pro issue- Power from Load icon
- Replies: 30
- Views: 5162
H3 Pro issue- Power from Load icon
Hey FOX People, please can you help me.
FOX H3 Pro with 2 x BMS and 17.9kw & 15.3kw of Battery, 52 Panels over 3 strings with a CHINT DTSO666 meter
Meter setup as
CT 1
PT 40
Prot N1
Add 1
Baud 9600
Net N34
Plu5 P 0
Disp 3
Blcd 30
Issue is
The batteries charge from the grid all by themselves, no ...
FOX H3 Pro with 2 x BMS and 17.9kw & 15.3kw of Battery, 52 Panels over 3 strings with a CHINT DTSO666 meter
Meter setup as
CT 1
PT 40
Prot N1
Add 1
Baud 9600
Net N34
Plu5 P 0
Disp 3
Blcd 30
Issue is
The batteries charge from the grid all by themselves, no ...
- Wed May 31, 2023 8:35 pm
- Forum: Customer/End User Help
- Topic: Hybrid 6KW H1 inverters in Parallel.
- Replies: 2
- Views: 2647
Hybrid 6KW H1 inverters in Parallel.
Can anyone advice how to wire and set up 2 x FOX ESS Hybrid 6kw Invertors as id like a total of 12KW supply. DO i need to set master & slave, any information please
We have
2 x H1-6.0-e Hybrid Inverters
2 x V2 BMS
6 x V2 HV2600 Batteries.
2 strings / arrays. 14 panels on each array.
I want to ...
We have
2 x H1-6.0-e Hybrid Inverters
2 x V2 BMS
6 x V2 HV2600 Batteries.
2 strings / arrays. 14 panels on each array.
I want to ...