Re: Displayed Load is always zero

All good now! Thanks for the advice.
by tromso
Thu Jan 30, 2025 4:37 pm
Forum: Customer/End User Help
Topic: Displayed Load is always zero
Replies: 5
Views: 6320

Re: Displayed Load is always zero

Thanks again Will.

I checked the inverter configuration (luckily, the default password was still valid) and, sure enough, the CT clamp function was shown as disabled, so I enabled it.

Just as I had finished doing so, the light level outside reduced enough for the inverter to go offline, so I will ...
by tromso
Thu Jan 30, 2025 3:56 pm
Forum: Customer/End User Help
Topic: Displayed Load is always zero
Replies: 5
Views: 6320

Re: Displayed Load is always zero

Hi Will, and thanks for the quick response.

I agree with you that a CT clamp is obviously necessary to measure the current, even though the Inverter manual implies that a CT clamp is only required for the export management function, so I have refitted the CT clamp onto the line cable into the house ...
by tromso
Thu Jan 30, 2025 11:18 am
Forum: Customer/End User Help
Topic: Displayed Load is always zero
Replies: 5
Views: 6320

Displayed Load is always zero

On 1st November 2024, 9 solar panels were installed on my house roofs in two arrays – the first of 5 panels, the second of 4 panels. Each panel has a nominal max output of 405 watts, giving a possible total of 3.6kW.

There was no battery storage required, so the inverter fitted was a Fox ESS F3600 ...