Hi Dave, thanks for replying so quickly.
I have set the output current to the maximum of 50A and the BMS is not throttling the current (I have been able to see on CAN traces that the discharge current transmitted fomr the BMS remains at 50A). I have been going through the thread on this forum ...
Search found 2 matches
- Thu Jun 20, 2024 11:05 am
- Forum: Customer/End User Help
- Topic: EPS overload at 1.5kW
- Replies: 3
- Views: 1191
- Thu Jun 20, 2024 9:42 am
- Forum: Customer/End User Help
- Topic: EPS overload at 1.5kW
- Replies: 3
- Views: 1191
EPS overload at 1.5kW
Good morning,
I have a KH10 fox inverter coupled with the ECS2800 fox batteries (x2 with total 5kWh), installation was relatively simple and have put a CAN logger between the battery and inverter to record messages and signals due to an EPS overload error I have been getting.
To my undertsanding ...
I have a KH10 fox inverter coupled with the ECS2800 fox batteries (x2 with total 5kWh), installation was relatively simple and have put a CAN logger between the battery and inverter to record messages and signals due to an EPS overload error I have been getting.
To my undertsanding ...