FoxEss T25 G3 series problem with Chint smart meter DTSU666CT

Post Reply
Krajcerr
Posts: 2
Joined: Thu Mar 16, 2023 9:00 pm

Hi to all !

Read and searching here for similiar problem but didn't find anything......

So I have fitted Chint dtsu666-CT (with ct's) , not regular in line dtsu666

I have strange readings....

In parameter I set CT ratio to 40, because ct's are 200A / 5A (=ratio 40........ok?)
And Ct's are in good position ....between House load / PV and Grid....and arrows are turned to house....

Phases are also correct A /B /C phase with A / B / C transformer

But I have odd readings, when PV production grow, also Load of house grows......PV product 12.5kw, Load is 9.2kw and 3.3kw "going to grid"
But I don't have 9kw consumption in house

It's seems to me that the box "Grid" is consumption of house, and box "Load" is actually grid.......is this possible?

oh, and I tryed to reverse the ct's arrows......then I have pv load 12.5 kw (ok)...... Load/consumption of house is 15.8 kw! and taking from Grid is 3.3kw....


Don't know what to do anymore 😓

Does anybody maybe have some solution?

Greeting!
Krajcerr
Posts: 2
Joined: Thu Mar 16, 2023 9:00 pm

Here is new info

On smart meter, the readings are fine

On inverter is abnormal....

Any sugesstion ?
Attachments
Screenshot_2023-03-17-07-18-30-488_com.fox.foxapp.jpg
IMG_20230317_071837.jpg
IMG_20230317_071858.jpg
IMG_20230317_071903.jpg
IMG_20230317_071908.jpg
varansolar
Posts: 1
Joined: Wed Apr 03, 2024 6:33 am

Hey! I have the same problem. Did you figure out the solution?