Thanks David.
read an Australian thread, I think they have a lot of the same issue.
One person suggested upping the cable size between the inverter and the mcb that ties you into the grid. I currently have a 6mm2 cable as per the manual with 40amp breaker.
If cable size is greater then ohms ...
Search found 2 matches
- Mon May 06, 2024 6:53 am
- Forum: Customer/End User Help
- Topic: Error Code 28 - 10 Minute Average Grid Voltage Fault
- Replies: 31
- Views: 42452
- Sat May 04, 2024 9:32 pm
- Forum: Customer/End User Help
- Topic: Error Code 28 - 10 Minute Average Grid Voltage Fault
- Replies: 31
- Views: 42452
Re: Error Code 28 - 10 Minute Average Grid Voltage Fault
Very useful thread.
My supplier attended and took a volt reading at 2100, it was 251. He explained that because I am close to the sub and further down the line there is a school the transformer is tapped fairly high to cater for the demand of the school that it can pull. This is why during non peak ...
My supplier attended and took a volt reading at 2100, it was 251. He explained that because I am close to the sub and further down the line there is a school the transformer is tapped fairly high to cater for the demand of the school that it can pull. This is why during non peak ...