Search found 5 matches

by Leiomerus
Thu Sep 28, 2023 9:15 pm
Forum: LV (Low Voltage)
Topic: LV5200 and Solis RHI-5K-48ES-5G - HighVolt.BMS(33293) Alarm
Replies: 15
Views: 6602

Re: LV5200 and Solis RHI-5K-48ES-5G - HighVolt.BMS(33293) Alarm

Hi everyone
The company that installed my batteries and the Solis inverter requested Solis to update the Solis inverter. Solis did that and now the BMS alarms are completely gone. I hope it will stay like this.

Regards
Leiomerus
by Leiomerus
Fri Sep 15, 2023 3:30 pm
Forum: LV (Low Voltage)
Topic: LV5200 and Solis RHI-5K-48ES-5G - HighVolt.BMS(33293) Alarm
Replies: 15
Views: 6602

Re: LV5200 and Solis RHI-5K-48ES-5G - HighVolt.BMS(33293) Alarm

Hi Jerry
I had some time today to raise a ticket with Foxess. I hope they will respond. Anyway, thanks for the advice !
Regards
Leiomerus
by Leiomerus
Tue Sep 12, 2023 10:27 pm
Forum: LV (Low Voltage)
Topic: LV5200 and Solis RHI-5K-48ES-5G - HighVolt.BMS(33293) Alarm
Replies: 15
Views: 6602

Re: LV5200 and Solis RHI-5K-48ES-5G - HighVolt.BMS(33293) Alarm

Hi I also have been reading in another forum, that it could help to lower the 'Floating Charge' in the control parameter settings. I lowered the floating charge to 51,0V, but still two alarms today. In the contral parameters of the Solis inverter there is also a 'Battery Overvoltage' of 60,0V and a ...
by Leiomerus
Tue Sep 12, 2023 10:04 pm
Forum: LV (Low Voltage)
Topic: LV5200 and Solis RHI-5K-48ES-5G - HighVolt.BMS(33293) Alarm
Replies: 15
Views: 6602

Re: LV5200 and Solis RHI-5K-48ES-5G - HighVolt.BMS(33293) Alarm

Hi All, I have the 6KW version of the OP's Solis inverter and 5 x LV5200 batteries. When I had 3, then 4 batteries I always used to get the High Volt alarm when they reached 100% SOC. When I added the 5th battery I had issues where the battery did not appear to be charging and was showing very odd ...
by Leiomerus
Tue Sep 12, 2023 8:41 pm
Forum: LV (Low Voltage)
Topic: LV5200 and Solis RHI-5K-48ES-5G - HighVolt.BMS(33293) Alarm
Replies: 15
Views: 6602

Re: LV5200 and Solis RHI-5K-48ES-5G - HighVolt.BMS(33293) Alarm

Hi everybody I experience about the same problems as almost everyone here. Since October last year, I have 23 solar panels, no problem with those. Normally a Solis inverter of 8 kW should be installed, but that one was not available. So the company asked me if an inverter of 5 Kw together with an So...